Zhejiang Dongfang Electromechanical Co., Ltd é um líder profissional China fonte de alimentação, fonte de alimentação dc, interruptor de alimentação, comutação de alimentação, levou fabricantes de fornecimento de energia e fornecedores com alta qualidade e baixo preço. Bem-vindo a entrar em contato conosco.
Model | DR-240-12 | DR-240-15 | DR-240-24 | DR-240-48 | |
Output | DC Voltage | 12V | 15V | 24V | 48V |
Voltage Tolerance | ±1% | ±1% | ±1% | ±1% | |
Rated Current | 20A | 16A | 10A | 5A | |
Current Range | 0~20A | 0~16A | 0~10A | 0~5A | |
Rated Power | 240W | 240W | 240W | 240W | |
Ripple & Noise | 100mVp-p | 100mVp-p | 100mVp-p | 150mVp-p | |
Voltage ADJ. range | 10.8~13.2V | 13.5~16.5V | 21.6~26.4V | 43.2~52.8V | |
Setup,rise time | 200ms,20ms/230VAC (at full load) | ||||
Hold up time | 20ms/230VAC (at full load) | ||||
Input | Voltage Range | 90-132VAC/180-264VAC selected by switch 255-370VDC | |||
Frequency | 47~63HZ | ||||
AC Current | 5A/115VAC 2.8A/230VAC | ||||
Efficiency | 85% | 84% | 85% | 86% | |
Inrush Current | Cold start 45A/230VAC 27A/115VAC | ||||
Leakage Current | < 3.5mA/240VAC | ||||
Protection | Overload | Rated output power 105%~150% start over load protection | |||
protection type:Constant current limiting, recovers automatically after fault condition is removed. | |||||
Over voltage | Protection type:Output voltage decline, recovers automatically after fault condition is removed | ||||
Environment | Working temp., humidity | -10℃~+60℃, 20%~90%RH non-condensing | |||
Storage temp., humidity | -20℃~+85℃, 10%~95%RH | ||||
Temp. Coefficient | ±0.03%/℃(0~45℃) | ||||
Withstand Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min., each along X, Y, Z axes | ||||
Safety | Withstand Voltage | I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |||
Isolated Resistance | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC/25℃/70%RH | ||||
Compliance | Safety Standard | Compliance to UL1012 | |||
EMC Standard | Compliance to EN55022, Class B, EN61000-6-1 | ||||
Others | Dimension | 125.2x125.2x100mm(LxWxH) | |||
Weight/packing | 1.1kg/12pcs/13.4kg | ||||
Note | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. |